Danh Mục

Micromaster MM440

MICROMASTER MM440

Overview
Application
The MICROMASTER 440 inverter is suitable for a variety of variable-speed drive applications. Its flexibility provides for a wide spectrum of applications. These also include cranes and hoisting gear, high-bay warehouses, production machines for food, beverages and tobacco, packaging machines etc.; i.e. applications which require the frequency inverter to have a higher functionality and dynamic response than usual.
The inverter is especially characterized by its customer-oriented performance and ease-of-use. Its large mains voltage range enables it to be used all over the world.
Design
The MICROMASTER 440 has a modular design. The operator panels and the modules can be easiliy exchanged.
International standards
The MICROMASTER 440 inverter complies with the requirements of the EU low-voltage guideline.
The MICROMASTER 440 inverter has the CE marking.
Acc. to UL and c UL certified
c-tick
Main characteristics
Easy, guided start-up
Modular construction allows maximum configuration flexibility
Six programmable isolated digital inputs
Two scaleable analog inputs (0 V to 10 V, 0 mA to 20 mA) can also be used as a 7th/8th digital input
Two programmable analog outputs (0 mA to 20 mA)
Three programmable relay outputs (30 V DC/5 A, resistive load; 250 V AC/2 A, inductive load)
Low-noise motor operation thanks to high pulse frequencies, adjustable (observe derating if necessary)
Protection for motor and inverter
Options (overview)
EMC filter, Class A/B
LC filter and sinusoidal filter 
Line commutating chokes
Output chokes
Gland plates
Basic Operator Panel (BOP) for parameterizing the inverter
Plain text Advanced Operator Panel (AOP) with multilanguage display
Plain text Asian Advanced Operator Panel (AAOP) with Chinese and English display
Plain text Cyrillic Advanced Operator Panel (CAOP) with Cyrillic, German and English display 
Communication modules
PROFIBUS
DeviceNet
CANopen
Pulse encoder evaluation module
PC connection kits
Mounting kits for installing the operator panels in the control cabinet doors
PC start-up tools, executable under Windows 98/NT/2000/XP Professional
TIA integration with Drive ES
Mechanical features
Modular design
Operating temperature
0.12 kW to 75 kW: -10 °C to +50 °C (+14 °F to +122 °F)
90 kW to 200 kW: 0 °C to +40 °C (+32 °F to +104 °F)
Compact housing as a result of high power density
Easy cable connection, mains and motor connections are separated for optimum electromagnetic compatibility
Detachable operator panels
Screwless control terminals on detachable I/O board
Performance features
Latest IGBT technology
Digital microprocessor control
High-quality Vector Control system
Flux Current Control (FCC) for improved dynamic response and optimized motor control
Linear V/f characteristic
Quadratic V/f characteristic
Multipoint characteristic (programmable V/f characteristic)
Torque control
Flying restart
Slip compensation
Automatic restart following mains failure or fault
User-definable function blocks for logic and arithmetic operations
Kinetic buffering
Positioning ramp down
High-grade PID controller for simple internal process control (autotuning)
Programmable acceleration/deceleration, 0 s to 650 s
Ramp smoothing
Fast Current Limit (FCL) for trip-free operation
Fast, repeatable digital input response time
Fine adjustment using two high-resolution 10-bit analog inputs
Compound braking for controlled rapid braking
Integrated brake chopper (only for 0.12 kW to 75 kW inverters)
Four skip frequencies
Removable “Y” capacitor for use on IT mains supplies (with non-grounded mains supplies, the “Y” capacitor must be removed, and an output choke installed)
Protection features
Overload capability
CT mode
0.12 kW to 75 kW:
Overload current 1.5 x rated output current (i.e. 150 % overload capability) for 60 s, cycle time 300 s,
and 2 x rated output current (i.e. 200 % overload capability) for 3 s, cycle time 300 s
90 kW to 200 kW:
Overload current 1.36 x rated output current (i.e. 136 % overload capability) for 57 s, cycle time 300 s,
and 1.6 x rated output current (i.e. 160 % overload capability) for 3 s, cycle time 300 s
VT mode
5.5 kW to 90 kW:
Overload current 1.4 x rated output current (i.e. 140 % overload capability) for 3 s,
and 1.1 x rated output current (i.e. 110 % overload capability) for 60 s, cycle time 300 s
110 kW to 250 kW:
Overload current 1.5 x rated output current (i.e. 150 % overload capability) for 1 s,
and 1.1 x rated output current (i.e. 110 % overload capability) for 59 s, cycle time 300 s
Overvoltage/undervoltage protection
Inverter overtemperature protection
Special direct connection for PTC or KTY to protect the motor
Earth fault protection
Short-circuit protection
I2t motor thermal protection
Locked motor protection
Stall prevention
Parameter interlock

Technical specifications
Technical data MICROMASTER 440
Mains voltage and power ranges   CT (constant torque) VT (variable torque)
200 V to 240 V 1 AC  ±10 % 0.12 kW to 3 kW -
200 V to 240 V 3 AC  ±10 % 0.12 kW to 45 kW 5.5 kW to 55 kW
380 V to 480 V 3 AC  ±10 % 0.37 kW to 200 kW 7.5 kW to 250 kW
500 V to 600 V 3 AC  ±10 % 0.75 kW to 75 kW 1.5 kW to 90 kW
Input frequency 47 Hz to 63 Hz
Output frequency in V/f mode for inverter 0.12 kW to 75 kW 0 ... 650 Hz, (limitation to 550 Hz in production to comply with legal requirements) 1)
for inverter 90 kW to 200 kW 0 Hz to 267 Hz
in vector mode for inverter 0.12 kW to 75 kW 0 Hz to 200 Hz
for inverter 90 kW to 200 kW 0 Hz to 200 Hz
Power factor ≥ 0.95
Inverter efficiency 0.12 kW to 75 kW: 96 % to 97 %; 90 kW to 200 kW: 97 % to 98 %
(Further information is available on the Internet at:
http://support.automation.siemens.com/WW/view/en/22978972)
Overload capability
CT mode
for inverter 0.12 kW to 75 kW Overload current 1.5 x rated output current (i.e. 150 % overload capability) for 60 s, cycle time 300 s, and 2 x rated output current (i.e. 200 % overload capability) for 3 s, cycle time 300 s
for inverter 90 kW to 200 kW Overload current 1.36 x rated output current (i.e. 136 % overload capability) for 57 s, cycle time 300 s, and 1.6 x rated output current (i.e. 160 % overload capability) for 3 s, cycle time 300 s
Overload capability
VT mode
for inverter 5.5 kW to 90 kW Overload current 1.4 x rated output current (i.e. 140 % overload capability) for 3 s, and 1.1 x rated output current (i.e. 110 % overload capability) for 60 s, cycle time 300 s
for inverter 110 kW to 250 kW Overload current 1.5 x rated output current (i.e. 150 % overload capability) for 1 s, and 1.1 x rated output current (i.e. 110 % overload capability) for 59 s, cycle time 300 s
Inrush current not higher than rated input current
Control method Vector control, torque control, linear V/f characteristic; quadratic V/f characteristic; multipoint characteristic (programmable V/f characteristic); flux current control (FCC)
Pulse frequency for inverter 0.12 kW to 75 kW 4 kHz (standard); 16 kHz (standard with 230 V inverters 0.12 kW to 5.5 kW)
2 kHz to 16 kHz (in 2 kHz steps)
for inverter 90 kW to 200 kW 2 kHz (standard with VT mode); 4 kHz (standard with CT mode)
2 kHz to 4 kHz (in 2 kHz steps)
Fixed frequencies 15, programmable
Skip frequency ranges 4, programmable
Setpoint resolution 0.01 Hz digital
0.01 Hz serial
10 bit analog
Digital inputs 6 fully programmable isolated digital inputs; switchable PNP/NPN
Analog inputs 2 programmable analog inputs
0 V to 10 V, 0 mA to 20 mA and -10 V to +10 V (AIN1)
0 V to 10 V and 0 mA to 20 mA (AIN2)
both can be used as 7th/8th digital input
Relay outputs 3, programmable
30 V DC/5 A (resistive load)
250 V AC/2A (inductive load)
Analog outputs 2, programmable (0/4 mA to 20 mA)
Serial interfaces RS-485, optional RS-232
Motor cable lengths Without output choke for inverter 0.12 kW to 75 kW max. 50 m (shielded)
max. 100 m (unshielded)
for inverter 90 kW to 250 kW max. 200 m (shielded)
max. 300 m (unshielded)
With output choke see variant dependent options
Electromagnetic compatibility (see Selection and Ordering Data) EMC filter, Class A or Class B to EN 55 011 available as an option
Inverter with internal filter Class A available
Braking Resistance braking with DC braking, compound braking, integrated brake chopper (integrated brake chopper only with 0.12 kW to 75 kW inverters)
Degree of protection IP20
Operating temperature (without derating) for inverter 0.12 kW to 75 kW CT: -10 °C to +50 °C (+14 °F to +122 °F)
VT: -10 °C to +40 °C (+14 °F to +104 °F)
for inverter 90 kW to 200 kW 0 °C to +40 °C (+32 °F to +104 °F)
Storage temperature -40 °C to +70 °C (-40 °F to +158 °F)
Relative humidity 95 % (non-condensing)
Installation altitude for inverter 0.12 kW to 75 kW up to 1000 m above sea level without derating
for inverter 90 kW to 200 kW up to 2000 m above sea level without derating
Standard SCCR
(Short Circuit Current Rating) 2)
FSA, FSB, FSC: 100 kA
FSD, FSE, FSF, FSFX, FSGX: 65 kA
Protection features for Undervoltage, overvoltage, overload, earth faults, short-circuits, stall prevention, locked motor protection, motor overtemperature, inverter overtemperature, parameter change protection
Compliance with standards uL, c uL, CE, c-tick
CE marking Conformity with low-voltage directive 73/23/EEC
Cooling-air volumetric flow required, dimensions and weights (without options) Frame size (FS) Cooling-air volumetric flow required (l/s)/(CFM) H x W x D, max. (mm) Weight, approx. (kg)
A 4.8/10.2 173 x 73 x 149 1.3
B 24/51 202 x 149 x 172 3.4
C 54.9/116.3 245 x 185 x 195 5.7
D 2 x 54.9/2 x 116.3 520 x 275 x 245 17
E 2 x 54.9/2 x 116.3 650 x 275 x 245 22
F without filter 150/317.79 850 x 350 x 320 56
F with filter 150/317.79 1150 x 350 x 320 75
FX 225/478.13 1400 x 326 x 356 116
GX 440/935 1533 x 326 x 545 174
  CFM:
Cubic Feet per Minute
   
           

1) For further information see http://support.automation.siemens.com/WW/view/en/107669667
2) Applies to industrial control cabinet installations to NEC article 409/UL 508A.
 
Derating data
Pulse frequency
Output Rated output current in A
for a pulse frequency of
kW 4 kHz 6 kHz 8 kHz 10 kHz 12 kHz 14 kHz 16 kHz
Mains operating voltage 200 V 1/3 AC 
0.12 to 5.5 Values correspond to the 4 kHz standard values. No derating, since 16 kHz standard.
7.5 28.0 26.6 25.2 22.4 19.6 16.8 14.0
11 42.0 37.8 33.6 29.4 25.2 21.0 16.8
15 54.0 48.6 43.2 37.8 32.4 27.0 21.6
18.5 68.0 64.6 61.2 54.4 47.6 40.8 34.0
22 80.0 72.0 64.0 56.0 48.0 40.0 32.0
30 104.0 91.0 78.0 70.2 62.4 57.2 52.0
37 130.0 113.8 97.5 87.8 78.0 71.5 65.0
45 154.0 134.8 115.5 104.0 92.4 84.7 77.0
Mains operating voltage 400 V 3 AC 
0.37 1.3 1.3 1.3 1.3 1.3 1.2 1.0
0.55 1.7 1.7 1.7 1.6 1.5 1.4 1.2
0.75 2.2 2.2 2.2 2.0 1.8 1.5 1.3
1.1 3.1 2.9 2.8 2.5 2.2 1.9 1.6
1.5 4.1 3.7 3.3 2.9 2.5 2.1 1.6
2.2 5.9 5.6 5.3 4.7 4.1 3.5 3.0
3.0 7.7 6.9 6.2 5.4 4.6 3.9 3.1
4.0 10.2 9.2 8.2 7.1 6.1 5.1 4.1
5.5 13.2 11.9 10.6 9.2 7.9 6.6 5.3
7.5 19.0 18.1 17.1 15.2 13.3 11.4 9.5
11.0 26.0 23.4 20.8 18.2 15.6 13.0 10.4
15.0 32.0 30.4 28.8 25.6 22.4 19.2 16.0
18.5 38.0 34.2 30.4 26.6 22.8 19.0 15.2
22 45.0 40.5 36.0 31.5 27.0 22.5 18.0
30 62.0 58.9 55.8 49.6 43.4 37.2 31.0
37 75.0 67.5 60.0 52.5 45.0 37.5 30.0
45 90.0 76.5 63.0 51.8 40.5 33.8 27.0
55 110.0 93.5 77.0 63.3 49.5 41.3 33.0
75 145.0 112.4 79.8 68.9 58.0 50.8 43.5
90 178.0 - - - - - -
110 205.0 - - - - - -
132 250.0 - - - - - -
160 302.0 - - - - - -
200 370.0 - - - - - -
Mains operating voltage 500 V 3 AC 
0.75 1.4 1.2 1.0 0.8 0.7 0.6 0.6
1.5 2.7 2.2 1.6 1.4 1.1 0.9 0.8
2.2 3.9 2.9 2.0 1.6 1.2 1.0 0.8
4.0 6.1 4.6 3.1 2.4 1.8 1.5 1.2
5.5 9.0 6.8 4.5 3.6 2.7 2.3  
Hiển thị:
Sắp xếp theo:
Màn hình AOP

Mã sản phẩm: 6SE6400-0AP00-0AA1

MICROMASTER 4 ADVANCED OPERATOR PANEL (AOP)..
0 VND
Kinh doanh và Hỗ trợ kỹ thuật
  • Hotline/Zalo: 0982.121.771
  • Liên hệ:  info@sistech.com.vn
  • Kỹ thuật: support@sistech.com.vn
Bài viết mới
TIA PORTAL V16 - DOWNLOAD TIA V16
Nối tiếp sự thành công của các phiên bản TIA Portal các version trước. Siemens cho ra đời một phiên bản phần mêm TIA mới nhất .. Chi tiết
GIỚI THIỆU CÁC DÒNG SẢN PHẨM S7-1500
► S7-1500 là bộ điều khiển thế hệ mới của TIA và là một cột mốc quan trọng trong hệ thống tự động hóa. ► S7-1500 với .. Chi tiết
TONG QUAN LOGO! 8
     Mô tả kỹ thuật: Logo! là một mô-đun logic thông dụng của Siemens, phù hợp cho những ứng dụng đ.. Chi tiết
Thư viện JSON cho PLC S7
JSON là một kiểu định dạng dữ liệu trong đó sử dụng văn bản thuần tuý, định dạng JSON sử dụng các cặp key - value để dữ liệu sử .. Chi tiết
  • Siemens
  • Banner
  • Monitor
  • Turck
Online
03285022
All days
Who's Online
3285022
7
Kết nối đến SISTECH
Bản quyền thuộc về Công ty TNHH Thương Mại Dịch Vụ Kỹ Thuật S.I.S © 2024 - Powered by SERENCO.NET